MAIN FEATURES

• 3 Phase mains (utility) sensing                                        

• Large LCD display with LED backlight and icons

• Compact dimensions                                                      

• AUTO-START and AMF (Automatic Mains Failure) controller forsingle gensets

• 3 Phase generator sensing                                             

• 3 CT inputs• True RMS measurements: kW, kVA, kVAr, pf, kWh (phase and total)

• 4 Configurable digital inputs                                          

• 3 Configurable analogue inputs + Configurable Charge alternator D+input

• Interface for traditional and J1939 engines                    

• USB serial port for configuration and FW update

•  Periodical test                                                                

• Remote start and stop

• Embedded alarm sounder                                             

• Real Time Clock with internal rechargeable Lithium battery

• Free configuration software                                           

• Data recording: 64 events log, 64 (slow) + 42 (fast) periodicalrecordings 

EMBEDDED FUNCTIONS

User-friendly symbols and codes for:

• Minimum/maximum voltage generator                        

• Minimum/maximum generator frequency

• Over speed                                                                    

• High coolant temperature

• Minimum fuel level                                                        

• Low battery voltage

• Failure engine CANBUS

Protective measures for all phases or for each single phase:

• Engine protection                                                          

• Fuel reserve

• Minimum/maximum fuel level                                       

• Minimum/maximum battery voltage

• Minimum/maximum oil pressure and temperature       

• Minimum/maximum coolant temperature

• Maximum power (32)                                                     

• Closing failure of mains contactor or genset contactor

• Engine over crank                                                           

• Over speed from generator frequency

• Belt breakage                                                                  

• Operating conditions not reached

• Emergency stop

Generator protection:                              

• Underfrequency (81U)                                                    

• Overfrequency (81O)

• Undervoltage (27)                                                           

• Overvoltage (59)

• Time dependent overcurrent (51)                                   

• Instantaneous overcurrent (50)

• Phases sequence (47)                                                      

• Currents and voltages unbalance (46/47)

Mains protection:

• Minimum/maximum mains voltage (27/59)                   

• Minimum/maximum mains frequency (81U/81O)

• Mains failure

TECHNICAL DATA

• Recommended operating temperature -30°C to +70°C

• Storage temperature -30°C to 80°C

• Dimensions: 142 (W) x 112 (H) x 41 (D) mm

• Cut-out dimensions 118 (W) x 92 (H) mm• Weight 250grammes

• Protection degree IP65 (with complimentary gasket)